GREAT BASIN UNIFIED AIR POLLUTION CONTROL DISTRICT

RULE 404-B - OXIDES OF NITROGEN
(Adopted 9/05/74; Revised 5/08/96)

1. Fuel Burning Equipment

A person shall not discharge from fuel burning equipment having a maximum heat input rate of more than 1 1/2 billion BTU per hour (gross), flue gas having a concentration of nitrogen oxides calculated as nitrogen dioxide (NO2) in parts per million parts of flue gas (ppm) by volume at 3 percent oxygen: 125 ppm with natural gas fuel, or 225 ppm with liquid or solid fuel.

2. Sources other than Combustion Sources

A person shall not discharge from sources other than combustion sources, nitrogen oxides, calculated as nitrogen dioxide (NO2): 250 part per million by volume.