MENDOCINO COUNTY AIR QUALITY MANAGEMENT DISTRICT
RULE 1-400 - BENZENE CONTROL FROM RETAIL SERVICE STATIONS
(a) PHASE I VAPOR RECOVERY SYSTEM REQUIREMENTS.
-
No owner or operator shall transfer, allow the transfer, or provide equipment
for the transfer of gasoline, and no other person shall transfer gasoline
from a gasoline delivery tank equipped with a vapor recovery system into
a stationary storage tank at a retail service station unless an ARB-certified
Phase I vapor recovery system is installed on the stationary storage tank
and used during the transfer. The ARB-certified Phase I vapor recovery
system shall meet a 90% vapor recovery efficiency as determined by ARB
Test Method 2-1 or equivalent.
-
The provisions of Rule 1-400 (a) (1) shall not apply to:
-
An existing retail service station with a gasoline throughput of 480,000
or fewer gallons during the calendar year 1988. If during any calendar
year thereafter the gasoline throughput at any existing retail service
station exceeds 480,000 gallons, this exemption shall cease to apply commencing
with the first day of the following calendar year.
-
A transfer to a stationary storage tank at an existing retail service station
which receives gasoline exclusively from delivery tanks that are not required
to be equipped with vapor recovery systems.
-
At the time of modifications at any existing retail service station of
any throughput, ARB-certified Phase I vapor recovery systems shall be installed
and used thereafter on all of the station facilities, except those stations
which are exempt from the Phase I requirement by Rule 1-400 (a) (2) (B).
(b) PHASE II VAPOR RECOVERY SYSTEM REQUIREMENTS.
-
No owner or operator shall transfer, allow the transfer or provide equipment
for the transfer of gasoline from a stationary storage tank at a retail
service station into a motor vehicle fuel tank unless an ARB-certified
Phase II vapor recovery system is installed and used during the transfer.
The ARB-certified Phase II vapor recovery system shall meet a 90% vapor
recovery efficiency as determined by ARB Test Method 2-1 or equivalent.
-
The provisions of Rule 1-400 (b)(1) shall not apply to an existing retail
service station which qualifies under the throughput exemption for Phase
I requirements of Rule 1-400 (a) (2) (A).
-
At the time of modifications at any existing retail service station of
any throughput, ARB-certified Phase II vapor recovery systems shall be
installed and used thereafter on all of the station facilities.
-
The operator of each retail facility utilizing a Phase II system shall
conspicuously post operating instructions for the system in the gasoline
dispensing area. The instructions shall clearly describe how to fuel vehicles
correctly with vapor recovery nozzles utilized at the station, and shall
include a warning that topping off may result in spillage or recirculation
of gasoline and is prohibited. Additionally, the instructions shall include
a prominent display of the District's or the ARB's toll free telephone
number for complaints.