SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT

RULE 260.153 - MONITORING OF OPERATIONS

(a) The owner or operator of any sludge incinerator subject to the provisions of this subpart shall:
 

  1. Install, calibrate, maintain, and operate a flow measuring device which can be used to determine either the mass or volume of sludge charged to the incinerator. The flow measuring device shall have an accuracy of +5 percent over its operating range.
  2. Provide access to the sludge charged so that a well-mixed representative grab sample of the sludge can be obtained.
  3. Install, calibrate, maintain, and operate a weighing device for determining the mass of any municipal solid waste charged to the incinerator when sewage sludge and municipal solid waste are incinerated together. The weighing device shall have an accuracy of +5 percent over its operating range.