SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT
RULE 260.112a - STANDARD FOR VOLATILE ORGANIC COMPOUNDS (VOC)
(a) The owner or operator of each storage vessel to which this subpart applies which contains a petroleum liquid
which, as stored, has a true vapor pressure equal to or greater than 10.3 kPa (1.5 psia) but not greater than 76.6
kPa (11.1 psia) shall equip the storage vessel with one of the following:
- An external floating roof, consisting of a pontoon-type or double-deck-type cover that rests on the surface
of the liquid contents and is equipped with a closure device between the tank wall and the roof edge. Except as
provided in Subsection (a)(1)(ii)(D) of this rule, the closure device is to consist of two seals, one above the
other. The lower seal is referred to as the primary seal and the upper seal is referred to as the secondary seal.
The roof is to be floating on the liquid at all times (i.e., off the roof leg supports) except during initial fill
and when the tank is completely emptied and subsequently refilled. The process of emptying and refilling when the
roof is resting on the leg supports shall be continuous and shall be accomplished as rapidly as possible.
(i) The primary seal is to be either a metallic shoe seal, a liquid-mounted seal, or a vapor-mounted seal. Each
seal is to meet the following requirements:
(A) The accumulated area of gaps between the tank wall and the metallic shoe seal or the liquid-mounted seal shall
not exceed 212 cm2per meter of tank diameter (10.0 in2 per ft. of tank diameter) and the
width of any portion of any gap shall not exceed 3.81 cm (1 1/2 in).
(B) The accumulated area of gaps between the tank wall and the vapor mounted seal shall not exceed 21.2 cm2
per meter of tank diameter (1.0 in2 per ft. of tank diameter) and the width of any portion of any gap
shall not exceed 1.27 cm (1/2 in).
(C) One end of the metallic shoe is to extend into the stored liquid and the other end is to extend a minimum
vertical distance of 61cm (24 in) above the stored liquid surface.
(D) There are to be no holes, tears, or other openings in the shoe, seal fabric, or seal envelope.
(ii) The secondary seal is to meet the following requirements:
(A) The secondary seal is to be installed above the primary seal so that it completely covers the space between
the roof edge and the tank wall except as provided in Subsection (a)(1)(ii)(B) of this rule.
(B) The accumulated area of gaps between the tank wall and the secondary seal used in combination with a metallic
shoe or liquid-mounted primary seal shall not exceed 21.2 cm2 per meter of tank diameter (1.0 in2
per ft. of tank diameter) and the width of any portion of any gap shall not exceed 1.27 cm (1/2 in). There shall
be no gaps between the tank wall and the secondary seal used in combination with a vapor mounted primary seal (that
equal or exceed 1/8 inch).
(C) There are to be no holes, tears or other
openings in the seal or seal fabric.
(D) The owner or operator is exempted from the requirements for secondary seals and the secondary seal gap criteria
when performing gap measurements or inspections of the primary seal.
(iii) Each opening in the roof except for automatic bleeder vents and rim space vents is to provide a projection
below the liquid surface. Each opening in the roof except for automatic bleeder vents, rim space vents and leg
sleeves is to be equipped with a cover, seal or lid which is to be maintained in a closed position at all times
(i.e., no visible gap) except when the device is in actual use or as described in Subsection (a)(1)(iv) of this
rule. Automatic bleeder vents are to be closed at all times when the roof is floating, except when the roof is
being floated off or is being landed on the roof leg supports. Rim vents are to be set to open when the roof is
being floated off the roof legs support or at the manufacturer's recommended setting.
(iv) Each emergency roof drain is to be provided with a slotted membrane fabric cover that covers at least 90 percent
of the area of the opening.
- A fixed roof with an internal floating type cover equipped with a continuous closure device between the
tank wall and the cover edge. The cover is to be floating at all times, (i.e., off the leg supports) except during
initial fill and when the tank is completely emptied and subsequently refilled. The process of emptying and refilling
when the cover is resting on the leg supports shall be continuous and shall be accomplished as rapidly as possible.
Each opening in the cover except for automatic bleeder vents and the rim space vents is to provide a projection
below the liquid surface. Each opening in the cover except for automatic bleeder vents, rim space vents, stub drains
and leg sleeves is to be equipped with a cover, seal, or lid which is to be maintained in a closed position at
all times (i.e., no visible gap) except when the device is in actual use. Automatic bleeder vents are to be closed
at all times when the cover is floating except when the cover is being floated off or is being landed on the leg
supports. Rim vents are to be set to open only when the cover is being floated off the leg supports or at the manufacturer's
recommended setting.
- A vapor recovery system which collects all VOC vapors and gases discharged from the storage vessel, and
a vapor return or disposal system which is designed to process such VOC vapors and gases so as to reduce their
emission to the atmosphere by at least 95 percent by weight.
- A system equivalent to those described in Subsections (a)(1), (a)(2), or (a)(3) of this rule as provided in
Rule 260.114a.
(b) The owner or operator of each storage vessel to which this subpart applies which contains a petroleum liquid
which, as stored, has a true vapor pressure greater than 76.6 kPa (11.1 psia), shall equip the storage vessel with
a vapor recovery system which collects all VOC vapors and gases discharged from the storage vessel, and a vapor
return or disposal system which is designed to process such VOC vapors and gases so as to reduce their emission
to the atmosphere by at least 95 percent by weight.