SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT
RULE 260.113b - TESTING AND PROCEDURES
(Rev. Effect. 10/16/90)
The owner or operator of each storage vessel as specified in Rule 260.112b(a) shall meet the requirements of Sections
(a), (b), or (c) of this rule. The applicable section for a particular storage vessel depends on the control equipment
installed to meet the requirements of Rule 260.112b.
(a) After installing the control equipment required to meet Rule 260.112b(a)(1) (permanently affixed roof and
internal floating roof), each owner or operator shall:
- Visually inspect the internal floating roof, the primary seal, and the secondary seal (if one is in service),
prior to filling the storage vessel with VOL. If there are holes, tears, or other openings in the primary seal,
the secondary seal, or the seal fabric or defects in the internal floating roof, or both, the owner or operator
shall repair the items before filling the storage vessel.
- For vessels equipped with a liquid-mounted or mechanical shoe primary seal, visually inspect the internal floating
roof and the primary seal or the secondary seal (if one is in service) through manholes and roof hatches on the
fixed roof at least once every 12 months after initial fill. If the internal floating roof is not resting on the
surface of the VOL inside the storage vessel, or there is liquid accumulated on the roof, or the seal is detached,
or there are holes or tears in the seal fabric, the owner or operator shall repair the items or empty and remove
the storage vessel from service within 45 days. If a failure that is detected during inspections required in this
section cannot be repaired within 45 days and if the vessel cannot be emptied within 45 days, a 30-day extension
may be requested from the Control Officer in the inspection report required in Rule 260.115b(a)(3). Such a request
for an extension must document that alternate storage capacity is unavailable and specify a schedule of actions
the company will take that will assure that the control equipment will be repaired or the vessel will be emptied
as soon as possible.
- For vessels equipped with a double-seal system as specified in Rule 260.112b(a)(1)(ii)(B):
- Visually inspect the internal floating roof, the primary seal, the secondary seal (if one is in service), gaskets,
slotted membranes (if any), and sleeve seals (if any) each time the storage vessel is emptied and degassed. If
the internal floating roof has defects, the primary seal has holes, tears, or other openings in the seal or the
seal fabric, or the secondary seal has holes, tears, or other openings in the seal or the seal fabric, or the gaskets
no longer close off the liquid surfaces from the atmosphere, or the slotted membrane has more than 10 percent open
area, the owner or operator shall repair the items as necessary so that none of the conditions specified in this
section exist before refilling the storage vessel with VOL. In no event shall inspections conducted in accordance
with this provision occur at intervals greater than 10 years in the case of vessels conducting the annual visual
inspection as specified in Subsections (a)(2) and (a)(3)(ii) of this rule and at intervals no greater than 5 years
in the case of vessels specified in Subsection (a)(3)(i) of this rule.
- Notify the Control Officer in writing at least 30 days prior to the filling or refilling of each storage vessel
for which an inspection is required by Subsections (a)(1) and (a)(4) of this rule to afford the Control Officer
the opportunity to have an observer present. If the inspection required by Subsection (a)(4) of this rule is not
planned and the owner or operator could not have known about the inspection 30 days in advance of refilling the
tank, the owner or operator shall notify the Control Officer at least 7 days prior to the refilling of the storage
vessel. Notification shall be made by telephone immediately followed by written documentation demonstrating why
the inspection was unplanned. Alternatively, this notification including the written documentation may be made
in writing and sent by express mail so that it is received by the Control Officer at least 7 days prior to the
refilling.
(b) After installing the control equipment required to meet Rule 260.112b(a)(2) (external floating roof), the
owner or operator shall:
- Determine the gap areas and maximum gap widths, between the primary seal and the wall of the storage vessel
and between the secondary seal and the wall of the storage vessel according to the following frequency.
(i) Measurements of gaps between the tank wall and the primary seal (seal gaps) shall be performed during the hydrostatic
testing of the vessel or within 60 days of the initial fill with VOL and at least once every 5 years thereafter.
(ii) Measurements of gaps between the tank wall and the secondary seal shall be performed within 60 days of
the initial fill with VOL and at least once per year thereafter.
(iii) If any source ceases to store VOL for a period of 1-year or more, subsequent introduction of VOL into
the vessel shall be considered an initial fill for the purposes of Subsections (b)(1)(i) and (b)(1)(ii) of this
rule.
- Determine gap widths and areas in the primary and secondary seals individually by the following procedures:
(i) Measure seal gaps, if any, at one or more floating roof levels when the roof is floating off the roof leg supports.
(ii) Measure seal gaps around the entire circumference of the tank in each place where a 0.32 cm (0.13 in) diameter
uniform probe passes freely (without forcing or binding against seal) between the seal and the wall of the storage
vessel and measure the circumferential distance of each such location.
(iii) The total surface area of each gap described in Subsection (b)(2)(ii) of this rule shall be determined
by using probes of various widths to measure accurately the actual distance from the tank wall to the seal and
multiplying each such width by its respective circumferential distance.
- Add the gap surface area of each gap location for the primary seal and the secondary seal individually
and divide the sum for each seal by the nominal diameter of the tank and compare each ratio to the respective standards
in Subsection (b)(4) of this rule.
- Make necessary repairs or empty the storage vessel within 45 days of identification in any inspection for seals
not meeting the requirements listed in Subsections (b)(4)(i) and (ii) of this rule.
(i) The accumulated area of gaps between the tank wall and the mechanical shoe or liquid-mounted primary seal shall
not exceed 212 cm2 per meter (10.0 in2 per foot) of tank diameter, and the width of any portion
of any gap shall not exceed 3.81 cm (1.5 in).
(A) One end of the mechanical shoe is to extend into the stored liquid, and the other end is to extend a minimum
vertical distance of 61 cm (24.0 in) above the stored liquid surface.
(B) There are to be no holes, tears, or other openings in the shoe, seal fabric, or seal envelope.
(ii) The secondary seal is to meet the following requirements:
(A) The secondary seal is to be installed above the primary seal so that it completely covers the space between
the roof edge and the tank wall except as provided in Subsection (b)(2)(iii) of this rule.
(B) The accumulated area of gaps between the tank wall and the secondary seal shall not exceed 21.2 cm2
per meter (1.0 in2 per foot) of tank diameter, and the width of any portion of any gap shall not exceed
1.27 cm (0.5 in).
(C) There are to be no holes, tears, or other openings in the seal or seal fabric.
(iii) If a failure that is detected during inspections required in Subsection (b)(1) of Rule 260.113b(b) cannot
be repaired within 45 days and if the vessel cannot be emptied within 45 days, a 30-day extension may be requested
from the Control Officer in the inspection report required by Rule 260.115b(b)(4). Such extension request must
include a demonstration of unavailability of alternate storage capacity and a specification of a schedule that
will assure that the control equipment will be repaired or the vessel will be emptied as soon as possible.
- Notify the Control Officer 30 days in advance of any gap measurements required by Subsection (b)(1) of this
rule to afford the Control Officer the opportunity to have an observer present.
- Visually inspect the external floating roof, the primary seal, secondary seal, and fittings each time the vessel
is emptied and degassed.
(i) If the external floating roof has defects, the primary seal has holes, tears, or other openings in the seal
or the seal fabric, or the secondary seal has holes, tears, or other openings in the seal or the seal fabric, the
owner or operator shall repair the items as necessary so that none of the conditions specified in this section
exist before filling or refilling the storage vessel with VOL.
(ii) For all the inspections required by Subsection (b)(6) of this rule, the owner or operator shall notify
the Control Officer in writing at least 30 days prior to the filling or refilling of each storage vessel to afford
the Control Officer the opportunity to inspect the storage vessel prior to refilling. If the inspection required
by Subsection (b)(6) of this rule is not planned and the owner or operator could not have known about the inspection
30 days in advance of refilling the tank, the owner or operator shall notify the Control Officer at least 7 days
prior to the refilling of the storage vessel. Notification shall be made by telephone immediately followed by written
documentation demonstrating why the inspection was unplanned. Alternatively, this notification including the written
documentation may be made in writing and sent by express mail so that it is received by the Control Officer at
least 7 days prior to the refilling.
(c) The owner or operator of each source that is equipped with a closed vent system and control device as required
in Rule 260.112b(a)(3) or (b)(2) (other than a flare) is exempt from Rule 260.8 of the General Provisions and shall
meet the following requirements:
- Submit for approval by the Administrator as an attachment to the notification required by Rule 260.7(a)(1)
or, if the facility is exempt from Rule 260.7(a)(1), as an attachment to the notification required by Rule 260.7(a)(2),
an operating plan containing the information listed below.
(i) Documentation demonstrating that the control device will achieve the required control efficiency during maximum
loading conditions. This documentation is to include a description of the gas stream which enters the control device,
including flow and VOC content under varying liquid level conditions (dynamic and static) and manufacturer's design
specifications for the control device. If the control device or the closed vent capture system receives vapors,
gases, or liquids other than fuels from sources that are not designated sources under this subpart, the efficiency
demonstration is to include consideration of all vapors, gases, and liquids received by the closed vent capture
system and control device. If an enclosed combustion device with a minimum residence time of 0.75 seconds and a
minimum temperature of 816° C (1500° F) is used to meet the 95 percent requirement, documentation that
those conditions will exist is sufficient to meet the requirements of this section.
(ii) A description of the parameter or parameters to be monitored to ensure that the control device will be
operated in conformance with its design and an explanation of the criteria used for selection of that parameter
(or parameters).
- Operate the closed vent system and control device and monitor the parameters of the closed vent system
and control device in accordance with the operating plan submitted to the Control Officer in accordance with Subsection
(c)(1) of this rule, unless the plan was modified by the Control Officer during the review process. In this case,
the modified plan applies.
(d) The owner or operator of each source that is equipped with a closed vent system and a flare to meet the
requirements of Rule 260.112b(a)(3) or (b)(2) shall meet the requirements as specified in the General Control Device
requirements, §60.18(e) and (f).