SAN JOAQUIN VALLEY UNIFIED AIR POLLUTION CONTROL DISTRICT
RULE 4304 - EQUIPMENT TUNING PROCEDURE FOR BOILERS, STEAM GENERATORS, AND PROCESS HEATERS
(Adopted October 19, 1995)
1.0 Purpose
The purpose of this rule is to provide an equipment tuning procedure for boilers, steam generators and process heaters to control visible emissions and emissions of both nitrogen oxides (NOx) and carbon monoxide (CO).
2.0 Applicability
This procedure applies to any boiler, steam generator, or process heater that requires tuning pursuant to District regulations or permit conditions.
3.0 Incorporation by Reference
The provisions of Attachment 4304-A and Attachment 4304-B are hereby adopted by reference and made a part hereof.
Attachment 4304-A
Equipment Tuning Procedure(1)
for Mechanical Draft Boilers, Steam Generators, and Process Heaters
Nothing in this Tuning Procedure shall be construed to require any act or omission that would result in unsafe conditions or would be in violation of any regulation or requirement established by Factory Mutual, Industrial Risk Insurers, National Fire Prevention Association, the California Department of Industrial Relations (Occupational Safety and Health Division), the Federal Occupational Safety and Health Administration, or other relevant regulations and requirements.
A different tuning procedure may be used if it produces equivalent results. Should a different tuning procedure be used, a copy of this procedure should be kept with the unit records for two years and made available to the District personnel on request.
a. Unacceptable flame conditions - such as flame impingement on furnace walls or burner parts, excessive flame carryover, or flame instability.
b. Stack gas CO concentrations greater than 400 ppm.
c. Smoking at the stack.
d. Equipment-related limitations - such as low windbox/furnace pressure differential, built in air-flow limits, etc.
|
Fuel |
Measurement |
Value |
|
Gaseous |
CO Emissions |
400 ppm |
|
#1 and #2 oils |
smoke-spot number |
number 1 |
|
#4 oil |
smoke-spot number |
number 2 |
|
#5 oil |
smoke-spot number |
number 3 |
|
Other oils |
smoke-spot number |
number 4 |
The above conditions are referred to as the CO or smoke thresholds, or as the minimum excess oxygen levels.
Compare this minimum value of excess oxygen to the expected value provided by the combustion unit manufacturer. If the minimum level found is substantially higher than the value provided by the combustion unit manufacturer, burner adjustments can probably be made to improve fuel and air mix, thereby allowing operations with less air.
Attachment 4304-B
Equipment Tuning Procedure
for Natural and Induced Draft-Boilers, Steam Generators, and Process Heaters.
Nothing in this Tuning Procedure shall be construed to require any act or omission that would result in unsafe conditions or would be in violation of any regulation or requirement established by Factory Mutual, Industrial Risk Insurers, National Fire Prevention Association, the California Department of Industrial Relations (Occupational Safety and Health Division), the Federal Occupational Safety and Health Administration, or other relevant regulations and requirements.
A different tuning procedure may be used if it produces equivalent results. Should a different tuning procedure be used, a copy of this procedure should be kept with the unit records for two years and made available to the District personnel on request.
a. Check the Operating Pressure or Temperature. Operate the boiler, steam generator, or process heater at the lowest acceptable pressure or temperature that will satisfy the load demand. This will minimize heat and radiation losses. Determine the pressure or temperature that will be used as a basis for comparative combustion analysis before and after tuneup.
b. Check Operating Hours. Plan the workload so that the boiler, steam generator, or process heater operates only the minimum hours and days necessary to perform the work required. Fewer operating hours will reduce fuel use and emissions. For units requiring a tuneup to comply with the rule, a totalizing non-resettable fuel meter will be required for each fuel used and for each boiler, steam generator, and process heater to prove fuel consumption is less than the heat input limit in Btu per year specified in the rule.
c. Check Air Supply. Sufficient fresh air supply is essential to ensure optimum combustion and the area of air supply openings must be in compliance with applicable codes and regulations. Air openings must be kept wide open when the burner is firing and clean from restriction to flow.
d. Check Vent. Proper venting is essential to assure efficient combustion. Insufficient draft or overdraft promotes hazards and inefficient burning. Check to be sure that vent is in good condition, sized properly and with no obstructions.
e. Combustion Analysis. Perform an "as is" flue gas analysis (O2, CO, CO2, etc.) at high and low fire, if possible. In addition to data obtained from combustion analysis, also record the following:
i. Inlet fuel pressure at burner (at high and low fire)


ii. Draft above draft hood or barometric damper
iii. Steam pressure, water temperature, or process fluid pressure or temperature entering and leaving the boiler, steam generator, or process heater.
iv. Unit rate if meter is available.
With above conditions recorded, make the following checks and corrective actions as necessary:
a. Check burner Condition. Dirty burners or burner orifices will cause boiler, steam generator, or process heater output rate and thermal efficiency to decrease. Clean burners and burner orifices thoroughly. Also, ensure that fuel filters and moisture traps in place, clean , and operating properly, to prevent plugging of gas orifices. Confirm proper location and orientation of burner diffuser spuds, gas canes, etc. Look for any burned-off or missing burner parts, and replace as needed.
b. Check for Clean Boiler, Steam Generator, or Process Heater Tubes and Heat transfer Surfaces. External and internal build-up of sediment and scale of the heating surfaces creates an insulating effect that quickly reduces unit efficiency. Excessive fuel cost will result if the units is not kept clean. Clean tube surfaces, remove scale and soot, assure proper fluid flow, and flue gas flow.
c. Check Water Treatment & Blowdown Program. Soft water and the proper water or process fluid treatment must be uniformly used to minimized scale and corrosion. Timely flushing and periodic blowdown must be employed to eliminate sediment and scale build-up on a boiler, steam generator, or process heater.
d. Check for Steam Hot Water or Process Fluid Leaks. Repair all leaks immediately since even small high pressure leaks quickly lead to considerate fuel, water and steam losses. Be sure there are no leaks through the blow-off drains, safety valve, by-pass lines or at the feed pump, if used.
a. Test primary and secondary low water level controls.
b. Check operating and limit pressure and temp. controls.
c. Check safety valve pressure and capacity to meet boiler, steam generator, or process heater requirements.
d. Check limit safety control and spill switch.
While taking combustion readings with a warmed up boiler, steam generator, or process heater at high fire perform checks and adjustments as follows:
a. Adjust unit to fire at rated capacity. Record fuel manifold pressure.
b. Adjust draft and/or fuel pressure to obtain acceptable, clean combustion at both high, medium and low fire. Carbon monoxide value should always be below 400 ppm at 3% O2. If CO is high make necessary adjustment. Check to ensure boiler, steam generator, or process heater light offs are smooth and safe. A reduced fuel pressure test at both high and low fire should be conducted in accordance with the manufacturers instructions and maintenance manuals.
c. Check and adjust operation of modulation controller. Ensure, proper efficient and clean combustion through range of firing rates. When above adjustments and corrections have been made, record all data.
Perform a final combustion analysis with a warmed up boiler, steam generator, or process heater at high, medium, and low fire, whenever possible. In addition to data from combustion analysis, also check and record:
a. Fuel pressure at burner (High, Medium, and Low).
b. Draft above draft hood or barometric damper (High, Medium, and Low).
c. Steam pressure or water temperature entering and leaving boiler, steam generator, or process heater.
d. Unit rate if meter is available.
When the above checks and adjustments have been made, record data and attach combustion analysis data to boiler, steam generator, or process heater records indicating name and signature of person, title, company name, company address and date the tuneup was performed.