SAN LUIS OBISPO COUNTY AIR POLLUTION CONTROL DISTRICT
RULE 425 - STORAGE OF VOLATILE ORGANIC COMPOUNDS
(Adopted 7/12/94)
A. APPLICABILITY
The provisions of this Rule shall apply to equipment used to store crude oil or volatile organic compounds (VOCs) with a vapor pressure greater than or equal to 0.50 pounds per square inch absolute (psia).
B. DEFINITIONS
a. The detection of total gaseous hydrocarbons for any component in excess of 10,000 ppmv as methane above background measured according to the test procedure in Subsection J.3, or
b. Exclusive of intermediate barrier seal fluids, any liquid leak which drips liquid organic compounds at the rate of more than three drops per minute or one (1) cubic centimeter per minute.
A "leak" is not a gaseous emission from pressure relief devices on tanks or delivery vessels when normal process pressure exceeds the limit specified for the device.
a. The discharge opening is entirely submerged when the liquid level is six (6) inches above the bottom of the container.
b. When applied to a container which is loaded from the side, the discharge opening is entirely submerged when the liquid level is 18 inches above the bottom of the container.
C. EXEMPTIONS
a. Any storage tank having a capacity of less than or equal to 1,500 gallons.
b. Any storage tank containing a volatile organic compound having a true vapor pressure of less than 0.50 psia. Organic compounds having the reference properties listed in Table 1 shall be deemed to be in compliance with the appropriate vapor pressure limits for the tank in which it is stored provided the actual storage temperature does not exceed the corresponding maximum temperature listed. Any person claiming exemption for a storage tank pursuant to Subsection C.1.b must maintain adequate records demonstrating that the true vapor pressure of all materials stored in that tank is less than 0.50 psia.
Table 1
|
Organic Compounds |
Reference Properties |
Maximum Temp. oF Not to Exceed |
|||
|
Density (lb/gal) |
oAPI |
IBP ( oF) |
0.5 psia (tvp) |
1.5 psia (tvp) |
|
| Middle Distillates | |||||
| Kerosene |
-- |
42.5 |
350 |
195 |
250 |
| Diesel |
-- |
36.4 |
372 |
230 |
290 |
| Gas Oil |
-- |
26.2 |
390 |
249 |
310 |
| Stove Oil |
-- |
23.0 |
421 |
275 |
340 |
| Jet Fuels |
|
|
|
|
|
| JP-1 |
-- |
43.1 |
330 |
165 |
230 |
| JP-3 |
-- |
54.7 |
110 |
-- |
25 |
| JP-4 |
-- |
51.5 |
150 |
20 |
68 |
| JP-5 |
-- |
39.6 |
355 |
205 |
260 |
| JP-7 |
-- |
44-50 |
360 |
205 |
260 |
| JP-8 |
-- |
-- |
-- |
167 |
222 |
| Fuel Oil |
|
|
|
|
|
| No. 1 |
-- |
42.5 |
350 |
195 |
250 |
| No. 2 |
-- |
36.4 |
372 |
230 |
290 |
| No. 3 |
-- |
26.2 |
390 |
249 |
310 |
| No. 4 |
-- |
23.0 |
421 |
275 |
340 |
| No. 5 |
-- |
19.9 |
560 |
380 |
465 |
| Residual |
-- |
19-27 |
-- |
405 |
-- |
| No. 6 |
-- |
16.2 |
625 |
450 |
-- |
| Asphalts |
|
|
|
|
|
| 60-100 pen. |
-- |
-- |
-- |
490 |
550 |
| 120-150 pen. |
-- |
-- |
-- |
450 |
500 |
| 200-300 pen. |
-- |
-- |
-- |
360 |
420 |
| Acetone |
6.6 |
47.0 |
133 |
-- |
35 |
| Acrylonitrile |
6.8 |
41.8 |
173 |
30 |
62 |
| Benzene |
7.4 |
27.7 |
176 |
34 |
70 |
| Carbon Disulfide |
10.6 |
22.1 |
116 |
-- |
10 |
| Carbon Tetrachloride |
13.4 |
-- |
170 |
20 |
63 |
| Chloroform |
12.5 |
-- |
142 |
-- |
40 |
| Cyclohexane |
6.5 |
49.7 |
177 |
30 |
65 |
| 1,2 Dichloroethane |
10.5 |
-- |
180 |
35 |
75 |
| Ethyl Acetate |
7.5 |
23.6 |
171 |
38 |
70 |
| Ethyl Alcohol |
6.6 |
47.0 |
173 |
55 |
85 |
| Isopropyl Alcohol |
6.6 |
47.0 |
181 |
62 |
95 |
| Methyl Alcohol |
6.6 |
47.0 |
148 |
30 |
62 |
| Methyl Ethyl Ketone |
6.7 |
44.3 |
175 |
30 |
70 |
| Toluene |
7.3 |
30.0 |
231 |
75 |
120 |
| Vinyl Acetate |
7.8 |
19.6 |
163 |
30 |
65 |
a. The tank is drained of volatile organic compounds or breakdown relief under Rule 107, Breakdown or Upset Conditions and Emergency Variances, is granted by the APCO.
b. Operation of the standby tank shall not occur beyond the period of the primary tank's breakdown and shall not exceed more than 15 calendar days per calendar year.
a. At least 72 hours prior to such work being done, verbal or written notice is received by the APCO.
b. For floating roof tanks, when the floating roof is resting on its leg supports, the process of filling, emptying, and refilling shall be continuous. Emissions shall be minimized during the process of filling, emptying, and refilling.
c. Vapor recovery shall be used on tanks so equipped during filling, flushing, and emptying procedures prior to opening tanks for cleanout.
d. A turn around report is submitted to the APCO no later than the first day of the quarter following the return to normal operation which provides information showing compliance with Subsection C.3. The first day of each quarter shall be considered January 1, April 1, July 1, and October 1 of any given year.
a. The tank is in compliance with this Rule prior to notification.
b. Product shall move neither in or out of the storage tank and emissions shall be minimized.
c. If an Authority to Construct is required in accordance with Rule 202, Permits, then it shall be obtained prior to commencing work.
d. The time of exemption allowed under this section shall not exceed 72 hours.
e. A maintenance report is submitted to the APCO no later than the first day of the quarter following the return to normal operation which provides information showing compliance with Subsection C.4. The first day of each quarter shall be considered January 1, April 1, July 1, and October 1 of any given year.
a. The tank is in compliance with this Rule prior to notification.
b. The APCO is notified when preventive maintenance work is completed.
c. Emissions are minimized during maintenance operations.
d. The time of exemption allowed under this section shall not exceed 24 hours.
e. A maintenance log is maintained which contains sufficient information to show compliance with Subsection C.5. That record shall be retained and available for inspection by District personnel for at least two (2) years.
D. STORAGE TANK REQUIREMENTS
a. A submerged fill pipe, or
b. One of the vapor loss control devices listed in Section E.
a. A pressure-vacuum relief valve set to within ten (10) percent of the maximum allowable working pressure of the tank or in accordance with appropriate recommendations of the American Petroleum Institute (API) or the American Society of Mechanical Engineers (ASME). The pressure-vacuum relief valve shall be properly installed, maintained in good operating order, and shall remain in a leak-free condition except when the operating pressure exceeds the valve set pressure; or
b. One of the vapor loss control devices in Section E.
a. A pressure tank maintaining working pressures sufficient at all times to prevent organic vapor loss to the atmosphere, or
b. Designed and equipped with a vapor loss control device listed in Subsection E.3 or E.4.
E. VAPOR LOSS CONTROL DEVICES
The following are the vapor loss control devices that satisfy the storage tank requirements of Section D.
Vapor recovery systems shall comply with the following requirements:
a. Any tank gauging or sampling device on a tank vented to the vapor recovery system shall be equipped with a leak-free cover which shall be closed at all times except during gauging or sampling.
b. All piping, valves and fittings shall be designed and constructed to operate in a leak-free condition, and shall be maintained and operated in a leak-free condition so as to minimize the release of volatile organic compound vapors.
c. Pressure-vacuum relief valves on above ground tanks shall be set to within ten (10) percent of the maximum allowable working pressure of the tank or in accordance with appropriate recommendations of the API or the ASME, and shall be properly installed, maintained in good operating order, and shall remain in a leak-free condition except when the operating pressure exceeds the valve set pressure.
F. REQUIREMENTS FOR ALL CLOSURE DEVICES
The closure device on any external floating roof tank or any internal floating roof tank shall meet the following requirements:
a. The well shall provide a projection of at least two (2) inches below the liquid surface.
b. The well shall be equipped with a cover, seal or lid, which shall at all times be in a closed position with no gap exceeding 1/8 inch, except when the well is in use.
c. In no case shall the gap between the well and the roof exceed 1/2 inch. The length of the gap between the well and the roof shall be added to the cumulative length of the gaps measured to determine compliance of the secondary seal as specified in Subsection G.2.c, G.3.a, G.4.b, or G.5.b.
a. The well shall provide a projection of at least two (2) inches below the liquid surface.
b. The well shall have an internal float designed to minimize the gap between the float and the well, provided that the gap in no case exceeds 1/2 inch.
c. In no case shall the gap between the well and the roof exceed 1/2 inch. The length of the gap between the well and the roof shall be added to the cumulative length of the gaps measured to determine compliance of the secondary seal as specified in Subsection G.2.c, G.3.a, G.4.b, or G.5.b.
a. One end of the shoe shall extend at least two (2) inches into the stored liquid and the other end shall extend a minimum vertical distance of 24 inches above the liquid surface.
b. The gap between the shoe and tank wall shall not exceed three (3) inches for a welded tank or five (5) inches for a riveted tank at any point from the liquid surface to 18 inches above it.
G. EXTERNAL FLOATING ROOF REQUIREMENTS
External floating roofs shall meet the following conditions in addition to the closure device requirements in Section F.
a. The cumulative length of all gaps between the primary seal and the tank shell exceeding 1/2 inch shall not be more than ten (10) percent, and exceeding 1/8 inch shall not be more than 40 percent of the tank circumference.
b. No gap between the tank shell and the primary seal shall exceed 1-1/2 inches; no continuous gap greater than 1/8 inch shall exceed ten (10) percent of the circumference of the tank.
c. The cumulative length of all gaps between the secondary seal and the tank shell exceeding 1/8 inch shall not be more than five (5) percent of the tank circumference.
d. No gap between the tank shell and the secondary seal shall exceed 1/2 inch.
e. The secondary seal shall allow easy insertion of probes up to 1-1/2 inches in width in order to measure gaps in the primary seal.
a. The cumulative length of all gaps between the tank shell and the primary or secondary seal exceeding 1/8 inch shall not be more than five (5) percent of the circumference of the tank.
b. No gap between the tank shell and the primary or secondary seal shall exceed 1/2 inch.
c. The secondary seal shall allow easy insertion of probes up to 1/2 inch in width in order to measure gaps in the primary seal.
d. The primary resilient toroid seal shall be liquid-mounted.
a. Gaps between the tank shell and the primary seal shall not exceed 2-1/2 inches. The cumulative length of all primary seal gaps exceeding 1-1/2 inches shall be not more than ten (10) percent of the circumference of the tank.
b. The secondary seal shall consist of at least two sealing surfaces, such that the sealing surfaces prevent the emission of volatile organic compounds around the rivets. Serrated sealing surfaces are allowable if the length of serration does not exceed six (6) inches. No gap between the tank shell and the secondary seal shall exceed 1/2 inch. The cumulative length of all secondary seal gaps exceeding 1/8 inch shall be not more than five (5) percent of the circumference.
a. No gap between the tank shell and the primary seal shall exceed 1-1/2 inches. No continuous gap in the primary seal greater than 1/8 inch shall exceed ten (10) percent of the circumference of the tank. The cumulative length of all primary seal gaps exceeding 1/2 inch shall be not more than ten (10) percent of the circumference and the cumulative length of all primary seal gaps exceeding 1/8 inch shall be not more than 40 percent of the circumference.
b. There shall be no visible or measurable gap between the tank shell and the secondary seal, excluding gaps less than two (2) inches from vertical weld seams.
a. Prior to installation of the secondary seal.
b. At least once every five (5) years, or once every ten (10) years if the seal is a zero gap secondary seal which is installed pursuant to Subsection G.5.
c. If the secondary seal is voluntarily removed by the owner or operator, it shall be made available for such inspection at that time. The owner or operator shall provide notification to the APCO no less than 72 hours prior to voluntary removal of the secondary seal.
H. INTERNAL FLOATING ROOF REQUIREMENTS
Internal floating roofs shall meet the following conditions in addition to the closure device requirements in Section F.
a. A liquid mounted primary seal only, mounted in full contact with the liquid in the annular space between the tank shell and floating roof, or
b. Both a primary and a secondary seal, one above the other.
I. INSPECTION REQUIREMENTS
J. TEST METHODS
a. If the API gravity of the oil is greater than or equal to 20 degrees, then the vapor pressure shall be determined by measuring the Reid vapor pressure and converting the result to true vapor pressure at the tank's maximum liquid storage temperature. For storage tanks operating above or below ambient temperatures, the maximum liquid storage temperature is the highest calendar-month average of the storage temperature. For storage tanks operating at ambient temperatures, the maximum liquid storage temperature is the maximum local monthly average ambient temperature as reported by the National Weather Service.
d. Separate samples shall be taken for API gravity and vapor pressure determinations. Sampling for API gravity shall be according to ASTM Method D-4057-88.
e. An alternative test method may be used if it provides the same result for a given sample and is approved in advance as a source-specific State Implementation Plan (SIP) revision by EPA and ARB for the purpose of determining vapor pressure of liquids of the type subject to this Rule.
a. ARB Method 202 applies to tanks receiving organic liquid by truck.
b. ARB Method 203 applies to tanks receiving organic liquid other than by truck.
K. RECORDKEEPING
a. Type of compound stored in each tank. The vapor pressure ranges of such compounds are required if records immediately available do not establish that the compound is a substance listed in Table 1 and kept below the temperature listed therein for that substance.
b. The settings of any pressure-vacuum relief valve and the basis for that setting.
c. The inspection reports required by Section I. Such records shall contain, at a minimum, the following information:
a. Permit number, tank identification, and type of vapor controls.
b. Description of specific maintenance procedure performed.
c. Estimate of emissions caused by maintenance procedure and description of estimation method.
d. Start and finish times and dates of procedure.
e. Copies of the reports required by Subsections C.3.d, C.4.e, and C.5.e.
L. REPORTING
No later than January 12, 1995, the owner or operator shall submit the following information to the APCO for each storage tank subject to this Rule:
M. VIOLATIONS
Any leak discovered by District personnel from equipment required to be leak-free shall constitute a violation of this Rule.
N. COMPLIANCE SCHEDULE