Refrigerant Management Program
Refrigerants Regulated
Refrigerants regulated under the Refrigerant Management Program include any refrigerant that is an ozone depleting substance as defined in Title 40 of the Code of Federal Regulation, Part 82, or any compound with a global warming potential (GWP) value equal to or greater than 150. The table below summarizes common high-GWP refrigerants regulated under the Refrigerant Management Program (highlighted in yellow) as well as alternative substitute refrigerants that are not regulated under the Refrigerant Management Program. The table only provides common refrigerants; it does not list all possible refrigerants that are regulated under the Refrigerant Management Program or all possible alternatives to these refrigerants.
| Common Refrigerants Regulated Under the Refrigerant Management Program and Non High-GWP Refrigerant Alternatives | ||||
| Refrigerant Designation | Refrigerant Name | Common Refrigerant Applications | Ozone Depleting Potential | Global Warming Potential |
| Chlorofluorocarbons (CFCs) | ||||
| R-11 | CFC-11 | Chillers | 1 | 3,800 |
| R-12 | CFC-12 | Chillers and Refrigeration Systems | 1 | 8,100 |
| R-114 | CFC-114 | Chillers | 1 | 10,000 |
| R-500 | CFC-500 | Chillers | 0.74 | 8,100 |
| R-502 | CFC-502* | Low Temperature Refrigeration Systems | 0.25 | 4,700 |
| Hydrochloroflourocarbons (HCFCs) | ||||
| R-22 | HCFC-22 | Chillers, Refrigeration Systems, and Air-conditioning Systems | 0.05 | 1,500 |
| R-123 | HCFC-123 | Chillers | 0.02 | 90 |
| Hydroflourocarbons (HFCs) | ||||
| R-23 | HFC-23 | Low Temperature Refrigeration Systems | 0 | 11,700 |
| R-125 | HFC-125 | Used in Refrigerant Blends | 0 | 2,800 |
| R-134a | HFC-134a | Chillers, Refrigeration Systems, and Air-conditioning Systems | 0 | 1,300 |
| R-143a | HFC-143a | Used in Refrigerant Blends | 0 | 3,800 |
| R-245fa | HFC-245fa | Chillers and Insulating Foams | 0 | 1,030 |
| R-404a | HFC-404a | Low Temperature Systems | 0 | 3,900 |
| R-407c | HFC-407c | Chillers, Refrigeration Systems, and Air-conditioning Systems | 0 | 1,800 |
| R-410a | HFC-410a | Air-conditioning Systems | 0 | 2,100 |
| R-507a | HFC-507a | Low Temperature Refrigeration Systems | 0 | 4,000 |
| Non high-GWP refrigerant alternatives not subject to the rule | ||||
| R-152a | HFC-152a | Used in Refrigerant Blends | 0 | 124 |
| R-744 | CO2 (Carbon Dioxide) | Refrigeration Systems | 0 | 1 |
| R-717 | NH3 (Ammonia) | Commercial and Industrial Refrigeration Systems | 0 | 0 |
* CFC/HCFC Blend
Join the Refrigerant Management Program email list for updates.
For questions on the rule or to provide feedback, please contact Refrigerant Management Program Staff at (916) 324-2517.