MOJAVE DESERT AIR QUALITY MANAGEMENT DISTRICT
RULE 1104 - ORGANIC SOLVENT DEGREASING OPERATIONS
(Adopted: September 28, 1994)
(A) General
(B) Definitions
(C) Standards
(a) All degreasers shall be equipped with the following:
(ii) A permanent, conspicuous label summarizing the applicable operating requirements contained in section (C)(2)(b).
In lieu of a label, operating instructions may be posted near the degreaser where the operators can access the
proper operating requirements of this rule.
(ii) A single or total drain hole area, not larger than 100 square centimeters (15.5 square inches) in area, for the solvent to flow from the sink (platform/work area) into the enclosed reservoir.
(iii) If high volatility solvent is used, a drain cover/plug/closure device or a cover for placement over the top of the sink (platform/work area), when the equipment is not being used, cleaned or repaired.
(iv) A minimum sink depth of six (6) inches, as measured from the top of the drain to the top of the side of the sink.
(ii) Cold solvent degreasers using only low volatility solvents may operate with a freeboard ratio equal to or greater than 0.50 when the cold solvent degreaser has a cover which remains closed during the cleaning operation.
(iii) Any cold solvent degreasers using solvent which is agitated, or heated above 50oC (120oF) shall operate with a freeboard ratio equal to or greater than 0.75.
(iv) A water cover may be used as an acceptable control method to meet the freeboard requirements, when the solvent is insoluble in water and has a specific gravity greater than 1.
(ii) Minimized entrance and exit openings which silhouette the work loads such that the average clearance between material and the edges of the cleaner openings are less than 10 centimeters (4 inches) or less than 10% of the opening width, whichever is greater.
(iii) A freeboard ratio equal to or greater than 0.75.
(iv) Alternately, a hood or enclosure to collect emissions which are vented to a control device may be used to satisfy requirement (e)(iii) above, provided that the overall efficiency (collection efficiency multiplied by the control efficiency) of the total system shall not be less than 85 percent by weight. The collection system shall have a ventilation rate of 15-20 cubic meters/min per square meter of solvent cleaner opening (at each air-vapor interface), unless the rate must be changed to meet Federal and State Occupational Safety and Health Administration requirements, and is approved in writing by the District APCO.
(ii) A vapor level control thermostat, a condenser flow switch and a spray safety switch.
(iii) A freeboard ratio greater than or equal to 0.75.
(iv) A primary condenser.
(v) In addition, degreasers with an evaporative surface area greater than or equal to one square meter, shall be equipped with a refrigerated freeboard chiller for which the chilled air blanket temperature (degrees F) at the coldest point on the vertical axis in the center of the air-vapor interface shall be no greater than 30 percent of the initial boiling point (degrees F) of the solvent used, or 40oF, which ever is greater. (If the chiller operates below the freezing temperature of water, it shall be equipped with an automatic defrost).
(vi) Alternately, a hood or enclosure to collect emissions which are vented to a control device may be used to satisfy the requirements of (d)(iii) and (d)(i) above, provided that the overall control efficiency (collection efficiency multiplied by the control efficiency) of the total system shall not be less than 85 percent by weight. The collection system shall have a ventilation rate of 15-20 cubic meters/min per square meter of solvent cleaner opening (at each air-vapor interface), unless the rate must be changed to meet Federal and/or State Occupational Safety and Health Administration requirements, and is approve in writing by the District Air Pollution Control Officer (APCO).
(ii) Minimized entrance and exit openings which silhouette the work loads such that the average clearance between material and the edges of the degreaser openings are less than 10 centimeters (4 inches) or less than 10 % of the opening, which ever is greater.
(iii) A primary condenser.
(iv) A freeboard ratio equal to or greater than 0.75.
(v) A vapor control thermostat, a condenser flow switch, and a spray safety switch.
(vi) Additionally, a refrigerated freeboard chiller for which the chilled air blanket temperature (degrees F) at the coldest point on the vertical axis in the center of the air-vapor interface shall be no greater than 30 percent of the initial boiling point (degrees F) of the solvent used, or 40oF, which ever is greater. (If the chiller operates below the freezing temperature of water, it shall be equipped with an automatic defrost).
(vii) Alternately, a hood or enclosure to collect emissions which are vented to a control device may
be used to satisfy requirements of sections (f)(iv) and (f)(vi) above, provided that the overall efficiency (collection
efficiency multiplied by the control efficiency) of the total system shall not be less than 85 percent by weight.
The collection system shall have a ventilation rate of 15-20 cubic meters/min per square meter of degreaser opening
(at each air-vapor interface), unless the rate must be changed to meet Federal and State Occupational Safety and
Health Administration requirements, and is approved in writing by the District APCO.
(a) All Degreasers shall comply with the following:
(ii) Degreasers shall not be operating with any detectable solvent leaks.
(iii) All solvent, including waste solvent and waste solvent residues, shall be stored in closed containers at all times. All containers for any solvent(s) shall have a label indicating the name of the solvent/material they contain.
(iv) Waste solvent and any residues shall be disposed of by one of the following methods: a commercial waste solvent reclamation service licensed by the State of California; or a federally or state licensed facility to treat, store or dispose of such waste; or the originating facility may recycle the waste solvent and materials in conformance with requirements of Section 25143.2 of the California Health and Safety Code.
(v) Degreasers shall be covered to prevent fugitive leaks of vapors, except when processing work or to perform maintenance.
(vi) Solvent carry-out shall be minimized by the following methods:
b) Limit the vertical speed of the power hoist to 3.3 meters per minute (11 ft/min) or less when such a hoist is used.
c) Retain the workload inside of the vapor zone until condensation ceases.
d) Tip out any pools of solvent remaining on the cleaned parts before removing them from the degreaser if the degreasers are operated manually.
e) Do not remove parts from the degreaser until the parts are visually dry and not dripping/leaking solvent. (This does not apply to an emulsion cleaner workload that is rinsed with water within the degreaser immediately after cleaning.)
(viii) Except for sealed chamber degreasers, all solvent agitation shall be by either pump recirculation, a mixer, or ultrasonics.
(ix) The solvent spray system shall be used in a manner such that liquid solvent does not splash outside of the container. The solvent spray shall be a continuous stream, not atomized or shower type, unless, the spray is conducted in a totally enclosed space, separated from the environment.
(x) For those degreasers equipped with a water separator, no solvent shall be visually detectable in the water in the separator.
(xi) Wipe cleaning materials containing solvent shall be kept in closed containers at all times, except during use.
(xii) A degreaser shall be located so as to minimize drafts being directed across the cleaning equipment, the exposed solvent surface, or the top surface of the vapor blanket.
(xiii) A method for draining cleaned material, such as a drying rack suspended above the solvent and within the freeboard area, shall be used so that the drained solvent is returned to the degreaser or container.
(ii) When shutting down the degreaser, the sump heater shall be turned off before, or simultaneously with, the cooling system.
(iii) The workload area shall not occupy more than half of the evaporative surface area of the degreaser.
(iv) Except for sealed chambers, the spray must be kept at least 10 centimeters (4 inches) below the top of the vapor level and be pointed downward, to prevent turbulence at the air-solvent vapor interface.
(ii) The sink of a remote reservoir degreaser or any container placed therein may not be used to soak a workload. Such use is prohibited and such use will cause the unit to be classified as a cold solvent degreaser and be subject to provisions of section (C)(1)(c) of this rule.
(iii) Parts shall be visually dry and not dripping/leaking solvent before being removed from the sink. Parts shall be tipped to release any trapped pools of solvent before being removed from the sink.
(iv) The workload must "drip-dry" while being contained completely within the sink.
(D) Prohibition
A lip exhaust system shall not be used on any degreaser unless it is vented to a hood or enclosure system as defined in section (C)(1)(e)(vi).
(E) Exemptions
(a) Solvents Containing Less Than 2% VOC: Solvent cleaning/degreasing operations using total liquid solvent containing less than 2 percent by weight of volatile organic compounds (VOC).
(b) Small Cold Solvent Degreasers: Any cold solvent degreaser with a solvent surface area of less than 929 square centimeters (1 square foot) shall meet the requirements of Section (C)(2)(a)(v) and (E)(2) of this rule.
(c) Consumer products such as aerosol cans or small containers (one quart or smaller) unless the total accumulative use is greater than 160 ounces (five quarts) of solvent per day. Persons using these products are subject to Section (C)(2)(a)(iii, iv & xi), Section (E)(2), Section (G)(a)(v) and Section (G)(c & d) of this rule.
(F) Administrative Requirements
Rule 442 Applicability: Any solvent using operation or facility which is not subject to this source-specific rule shall comply with the provisions of Rule 442. Any solvent using operation or facility which is exempt from all or a portion of the VOC limits, equipment limits or the operational limits of this rule shall be subject to the applicable provisions of Rule 442.
(G) Recordkeeping Requirements
(a) Maintain and have available during an inspection, a current list of solvents in use at the facility which provides all of the data necessary to evaluate compliance, including the following information separately for each degreaser, as applicable:
(ii) the mix ratio of solvent compounds mixtures of solvents are used, and
(iii) VOC content of solvent or mixture of compounds as used, and
(iv) the total volume of the solvent(s) used for the facility, on a monthly basis, and
(v) the name and total volume applied of wipe cleaning solvent(s) used, on a monthly basis.
(c) Documentation shall be maintained on site of the disposal or on site recycling of any waste solvent or residues.
(d) Such records shall be retained on site (at the facility) and available for inspection by the Air Pollution
Control Officer for the previous 24 month period.
(H) Test Methods
(a) Determination of the VOC Content of Solvent Samples The determination of the volatile organic compound content shall be by the appropriate procedures contained in EPA Method 24.
(b) Determination of Initial Boiling Point of Solvents The initial boiling point of the solvent shall be determined by ASTM Test Method D1078-86.
(d) Determination of Capture Efficiency Capture efficiency shall be determined by the appropriate procedures set out in 40 CFR 52.741 appendix B.
(e) Determination of Control Efficiency EPA Method 25, EPA Method 25A, or ARB Method 100 shall be used to determine control efficiency.
(f) Determination of the Ventilation/Draft Rate The ventilation/draft rate shall be determined by EPA Methods 2, 2A, 2C and 2D.
(g) Determination of Exempt Compounds Determination of the exempt compounds, shall be performed in accordance
with ASTM Test Method D 4457-85 (Solvents and Coatings) and be consistent with the provisions set forth in the
Federal Register (FR, Vol. 56, No. 52, March 18, 1991). Perfluorocarbon compounds shall be assumed to be absent
from a product or process unless a manufacturer or facility operator identifies a specific compound or compounds
from the broad classes of perfluorocarbons listed in 40 CFR 51.100(S)(1) as being present in the product or process.
When such compounds are identified, the facility shall provide the test method to determine the amount(s) of the
specific compound(s).
(I) Compliance Schedule
Any person subject to any of the requirements of this rule shall comply with the following increments of progress: