SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT

RULE 2012 - CHAPTER 7 - REMOTE TERMINAL UNIT (RTU) ELECTRONIC REPORTING
(Amended April 9, 1999)

TABLE OF CONTENTS


A. General............................................................................................ 2012A-7-1

B. Products........................................................................................... 2012A-7-3

C. Execution......................................................................................... 2012A-7-5

D. Data Requirements........................................................................... 2012A-7-10

Appendix G - Diagrams........................................................................ 2012A-7-22

This chapter defines the tasks and characteristics for electronic reporting of emissions from all sources. The Facility Permit holder of a major source shall use an RTU to telecommunicate rule compliance data to the District Central Station Emissions Monitoring Computer. The RTU shall collect data, perform calculations, generate the appropriate data files, and transmit the data to the Central Station. The Facility Permit holder of a large source or process unit may elect to use an RTU. Alternatively, the Facility Permit holder of a large source or process unit shall compile the required rule compliance data manually, and transmit that data via modem in accordance with the data requirements of Section D in this chapter.

A. GENERAL

    1. General

    The Facility Permit holder of a major source shall telecommunicate rule compliance data to the District via Remote Terminal Units (RTU). This form of reporting may also be used for large sources or process units. The RTU shall collect data from a CEMS, a CPMS, or other equipment specified in the Facility Permit and send data periodically to the Central Station Emissions Monitoring Computer (Central Station ).

    This chapter specifies the tasks and characteristics required of the RTU and shall be used as a guide for providing the required software/hardware for the RTU. Emissions Data Collection System conformity as well as establishing and maintaining communications with the emission monitoring system and the Central Station shall be the responsibility of the Facility Permit holder. This chapter also serves as a functional guideline for operating requirements of the RTU, and provides information concerning RTU hardware/software procurement, configuration, installation, maintenance, and compatibility with the emission monitoring system and the Central Station.

    2. RTU and Supporting Equipment Description

B. PRODUCTS

    1. RTU Attributes

C. EXECUTION

    1. General

    2. Project Plan

    Develop a project plan for accomplishing the requirements of this installation . The plan shall include a checklist for the Submittal date .

    3. Software Requirements Guideline

    The Software Requirement Guideline (SRG) shall specify tasks and characteristics required of the RTU and is to be used as a guide for providing the required software for the RTU. Emissions Data Collection System conformity as well as establishing and maintaining communications with the emission monitoring system and the Central Station shall be the responsibility of the Facility Permit holder.

    4. Required Installation Practices

    5. Submittals

D. DATA REQUIREMENTS

    1. General Requirements

    The District will accept data in the American Standard Code for Information Interchange (ASCII) format.

    The data file structure must be sequential. The record delimiter - a ~ (tilde) occurs only once following the end of each data record. There must be no delimiter before the first data record. The ASCII value for the delimiter is:
    ~ (decimal 126)

    Blank data records must not be reported

    In text fields, only upper case characters are to be used and must be left justified. Text fields that are not applicable must be filled with blanks. The ~ character (decimal 126) must never appear inside text fields.

    Numeric fields must be right justified and zero filled. Where decimal places are to be reported, they are to be implied - do not include the decimal point character. Numeric fields that are zeros or not applicable, must be zero filled.

    Date fields must be entered in the format "YYYYMMDD" and must always specify a valid date.

    2. Data File Description

    A properly composed data file is comprised of the following data records (shown indented to illustrate the logical grouping):

    Code 1A

    -

    Transmitter Record
    Code 1F

    -

    Facility Record
    Emission data record(s) from any of the following data records
    Code 1NP

    -

    NOx Process Unit and Large Source Record
    Code 1NM

    -

    NOx Major Source Record
    Code 1SP

    -

    SOx Process Unit Record
    Code 1SM

    -

    SOx Major Source Record
    Code 1FT

    -

    Facility Total Record
    Code 1F

    -

    Facility Record
    Emission data record(s)
    Code 1FT

    -

    Facility Total Record
    Code 1T

    -

    Final Total Record

    The Code 1A data record identifies the facility submitting the data file and must be the first data record in the data file.

    The Code 1T data record identifies the end of a data file and must be the last data record in the data file

    The Code 1F data record identifies the facility whose emission data records are being reported.

    The Code 1FT data record identifies the end of emission data records for a particular facility.

    Code 1F/1FT data records must not be nested inside of another 1F/1FT group and are repeated for each facility to be reported.

    Emission data records for a facility are reported following the Code 1F but before the 1FT data record for that facility and can comprise any of the following data record types:

    Code 1NP

    -

    NOx Process Unit and Large Source Record
    Code 1NM

    -

    NOx Major Source Record
    Code 1SP

    -

    SOx Process Unit Record
    Code 1SM

    -

    SOx Major Source Record

The following table summarizes valid Record Identifiers to be used starting January 1, 1998 to perform electronic reporting via a RTU or modem. The 1A through 1T records are used for identification and grouping purposes. The 1NP through 1SM records are the pre-existing emissions reporting records. Starting January 1, 1998, these records may only be used for devices which do not use multiple fuels and are not involved in multiple processes. Otherwise, sources shall report emissions by each fuel type or process conducted within the reporting period. If more than 50% of the emissions from a source is from the combustion of fuels, the emission report for such a source or process unit shall be reported based on the fuel combusted. Otherwise, emissions shall be reported based on the Source Classification Code (SCC) for the process conducted. The 1NPF through 1SUQ records are utilized for reporting emissions from devices with multiples fuels or processes. Record Identifiers starting with "2" are used to make corrections to submitted electronic emissions reports. Record Identifiers starting with "3" are used to delete previously submitted electronic emissions reports which were filed erroneously. Erroneous records to be corrected need not be deleted first.

Record Identifiers Summary Table

Record Identifier for

 

Adding a record

Updating a record

Deleting a record

Description

1A*

--

--

Transmitter Record

1F*

--

--

Facility Record

1FT*

--

--

Facility Total Record

1T*

--

--

Final Total Record

1NP*

2NP

3NP

NOx Emissions Report for Process Units

1NL*

2NL

3NL

NOx Emissions Report for Large Sources

1NM*

2NM

3NM

NOx Emissions Report for Major Sources

1SP*

2SP

3SP

SOx Emissions Report for Process Units

1SM*

2SM

3SM

SOx Emissions Report for Major Sources

1NPF

2NPF

3NPF

NOx Emissions Report for Process Units by Fuel Type

1SPF

2SPF

3SPF

SOx Emissions Report for Process Units by Fuel Type

1NLF

2NLF

3NLF

NOx Emissions Report for Large Sources by Fuel Type

1NMF

2NMF

3NMF

NOx Emissions Report for Major Sources by Fuel Type

1SMF

2SMF

3SMF

SOx Emissions Report for Major Sources by Fuel Type

1NPS

2NPS

3NPS

NOx Emissions Report for Process Units by SCC

1SPS

2SPS

3SPS

SOx Emissions Report for Process Units by SCC

1NLS

2NLS

3NLS

NOx Emissions Report for Large Sources by SCC

1NMS

2NMS

3NMS

NOx Emissions Report for Major Sources by SCC

1SMS

2SMS

3SMS

SOx Emissions Report for Major Sources by SCC

1NMM

2NMM

3NMM

Monthly NOx Emissions Report for Major Sources

Record Identifers Summary Table (Continued)

Record Identifier for

 

Adding a record

Updating a record

Deleting a record

Description

1SMM

2SMM

3SMM

Monthly SOx Emissions Report for Major Sources

1NMQ

2NMQ

3NMQ

Quarterly NOx Emissions Report for Major Sources

1SMQ

2SMQ

3SMQ

Quarterly SOx Emissions Report for Major Sources

1NLQ

2NLQ

3NLQ

Quarterly NOx Emissions Report for Large Sources

1NRF

2NRF

3NRF

Quarterly NOx Emissions Report by fuel type for Rule 219 Exempt Equipment

1SRF

2SRF

3SRF

Quarterly SOx Emissions Report by fuel type for Rule 219 Exempt Equipment

1NRS

2NRS

3NRS

Quarterly NOx Emissions Report by SCC for Rule 219 Exempt Equipment

1SRS

2SRS

3SRS

Quarterly SOx Emissions Report by SCC for Rule 219 Exempt Equipment

1NVF

2NVF

3NVF

Quarterly NOx Emissions Report by fuel type for Equipment Operating under a Various Locations Permit

1SVF

2SVF

3SVF

Quarterly SOx Emissions Report by fuel type for Equipment Operating under a Various Locations Permit

1NVS

2NVS

3NVS

Quarterly NOx Emissions Report by SCC for Equipment Operating under a Various Locations Permit

1SVS

2SVS

3SVS

Quarterly SOx Emissions Report by SCC for Equipment Operating under a Various Locations Permit

1NWF

2NWF

3NWF

Quarterly NOx Emissions Report by fuel type for Equipment Operating Without Permit or District assigned Device IDs

1SWF

2SWF

3SWF

Quarterly SOx Emissions Report by fuel type for Equipment Operating Without Permit or District assigned Device IDs

1NWS

2NWS

3NWS

Quarterly NOx Emissions Report by SCC for Equipment Operating Without Permit or District assigned Device IDs

1SWS

2SWS

3SWS

Quarterly SOx Emissions Report by SCC for Equipment Operating Without Permit or District assigned Device IDs

1NPQ

2NPQ

3NPQ

Quarterly NOx Aggregate Emissions Report for Process Units

1SPQ

2SPQ

3SPQ

Quarterly SOx Aggregate Emissions Report for Process Units

1NXQ

2NXQ

3NXQ

Quarterly NOx Aggregate Emissions Report for Rule 219 Exempt Equipment

1SXQ

2SXQ

3SXQ

Quarterly SOx Aggregate Emissions Report for Rule 219 Exempt Equipment

* Previously defined codes

Record Identifers Summary Table (Continued)

Record Identifier for

 

Adding a record

Updating a record

Deleting a record

Description

1NTQ

2NTQ

3NTQ

Quarterly NOx Aggregate Emissions Report for Equipment Operating under a Various Locations Permit

1STQ

2STQ

3STQ

Quarterly SOx Aggregate Emissions Report for Equipment Operating under a Various Locations Permit

1NUQ

2NUQ

3NUQ

Quarterly NOx Aggregate Emissions Report for Equipment Operating without a Permit

1SUQ

2SUQ

3SUQ

Quarterly SOx Aggregate Emissions Report for Equipment Operating without a Permit

* Previously defined codes

Code 1A - Transmitter Record

The Code 1A data record is used to identify the facility submitting the data file and must be the first data record reported.

Location Field

Length

Description
1-4 Record Identifier

4

Constant "1A" followed by 2 blanks.
5-10 SCAQMD Facility ID

6

The 6-digit SCAQMD facility ID of the facility submitting the data file.
11-128 Filler

118

Blanks , used to fill unused remaining record positions.

Code 1F - Facility Record

The Code 1F data record is used to identify the facility whose emissions are being reported.

Location Field

Length

Description
1-4 Record Identifier

4

Constant "1F" followed by 2 blanks.
5-10 SCAQMD Facility ID

6

The 6-digit SCAQMD facility ID for the facility whose emissions are being reported.
11-128 Filler

118

Blanks , used to fill unused remaining record positions.

Code 1FT - Facility Total Record

The Code 1FT data record is used to identify the end of data emission records for a facility.

Location Field

Length

Description
1-4 Record Identifier

4

Constant "1FT" followed by 1 blank.
5-11 Number of Emission

Data Records

7

The total number of emission data records reported for the facility (excluding the 1F and the 1FT data records). Right justify and zero fill.
12-128 Filler

117

Blanks , used to fill unused remaining record positions.

Code 1T - Final Total Record

The Code 1T data record is used to identify the end of the data file and must be the last data record reported.

Location Field

Length

Description
1-4 Record Identifier

4

Constant "1T" followed by 2 blanks
5-11 Number of Data

7

The total number of data records reported (including the Code 1T) in the data file. Right justify and zero fill.
12-128 Filler

117

Blanks , used to fill unused remaining record positions.

Code 1NP and 1NL- NOx Process Unit and Large Source Record

The Code 1NP data record is used to report NOx emissions from NOx Process Units with SCAQMD assigned Device Ids. The Code 1NL data record is used to report NOx emissions from NOx Large Sources with SCAQMD assigned Device IDs. Starting January 1, 1998, these records shall only be used for devices which do not use multiple fuels and are not involved in multiple processes.

Location Field Length Description
1-4 Record Identifier

4

"1NP" or "1NL"followed by 1 blank
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-27 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
28 - 128 Filler

101

Blanks , used to fill unused remaining record positions

Code 1NM - NOx Major Source Record

The Code 1NM data record is used to report NOx emissions from Major NOx sources with SCAQMD assigned Device IDs. Starting January 1, 1998, this record shall only be used for devices which do not use multiple fuels and are not involved in multiple processes.

Location Field Length Description
1-4 Record Identifier

4

Constant "1NM" followed by 1 blank
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-27 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
28-36 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
37 - 128 Filler

92

Blanks , used to fill unused remaining record positions

Code 1SP - SOx Process Unit Record

The Code 1SP data record is used to report SOx emissions from SOx Process Units with SCAQMD assigned Device IDs. Starting January 1, 1998, this record shall only be used for devices which do not use multiple fuels and are not involved in multiple processes.

Location Field Length Description
1-4 Record Identifier

4

Constant "1SP"followed by 1 blank
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-27 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
28 - 128 Filler

101

Blanks , used to fill unused remaining record positions

Code 1SM - SOx Major Source Record

The Code 1SM data record is used to report SOx emissions from Major SOx sources with SCAQMD assigned Device IDs. Starting January 1, 1998, this record shall only be used for devices which do not use multiple fuels and are not involved in multiple processes.

Location Field Length Description
1-4 Record Identifier

4

Constant "1SM" followed by 1 blank
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-27 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
28-36 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
37 - 128 Filler

92

Blanks , used to fill unused remaining record positions

Code 1NMF and 1SMF - NOx and SOx Major Source Emissions Report by Fuel Type

The Codes 1NMF and 1SMF data records are used to report NOx and SOx emissions by fuel type from Major SOx sources with SCAQMD assigned Device IDs. Starting January 1, 1998, these records shall be used to report emissions from each Major SOx sources and each fuel used during a reporting day.

Location Field Length Description
1-4 Record Identifier

4

1NMF or 1SMF
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-38 Fuel Type

20

Code for Fuel Type utilized. Left justified, blank filled
39-47 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
48-56 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
57 - 128 Filler

72

Blanks , used to fill unused remaining record positions

Code 1NMS and 1SMS - NOx and SOx Major Source Emissions Report by SCC

The Codes 1NMS and 1SMS data records are used to report NOx and SOx emissions by Source Classification Codes (SCC) from Major SOx sources with SCAQMD assigned Device IDs. Starting January 1, 1998, these records shall be used to report emissions from each Major SOx sources and each process conducted during a reporting day.

Location Field Length Description
1-4 Record Identifier

4

1NMS or 1SMS
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

The date emitted in the format "YYYYMMDD"
19-26 SCC

8

Source Classification Code
27-35 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
36-44 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
45 - 128 Filler

84

Blanks , used to fill unused remaining record positions

Code 1NLF, 1NPF and 1SPF - NOx Large Source and NOx and SOx Process Unit Emissions Report by Fuel Type

The Codes 1NLF, 1NPF and 1SPF data records are used to report NOx and SOx emissions by fuel type from NOx Large source, NOx and SOx Process Units, respectively, with SCAQMD assigned Device IDs. Starting January 1, 1998, these records shall be used to report emissions from each device and each fuel used during a reporting period.

Location Field Length Description
1-4 Record Identifier

4

1NLF, 1NPF, or 1SPF
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

End date of reporting period in the format "YYYYMMDD"
19-38 Fuel Type

20

Code for Fuel Type utilized. Left justified, blank filled
39-47 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
48-56 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
57 - 128 Filler

72

Blanks , used to fill unused remaining record positions

Code 1NLS, 1NPS and 1SPS - NOx Large Source and NOx and SOx Process Units Emissions Report by SCC

The Codes 1NLS, 1NPS and 1SPS data records are used to report NOx and SOx emissions by SCC from NOx Large source, NOx and SOx Process Units, respectively, with SCAQMD assigned Device IDs. Starting January 1, 1998, these records shall be used to report emissions from each device and each process conducted during a reporting period.

Location Field Length Description
1-4 Record Identifier

4

1NLS, 1NPS, or 1SMS
5-10 SCAQMD Device ID

6

The SCAQMD assigned Device IDs for the equipment source. Left justify and fill with blanks
11-18 Date Emitted

8

End date of reporting period in the format "YYYYMMDD"
19-26 SCC

8

Source Classification Code
27-35 Total Emission

9(#######.##)

The total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
36-44 Status Word

9

The nine character status word for the reporting day from the Status Word Table.
45 - 128 Filler

84

Blanks , used to fill unused remaining record positions

Code 1NMM, 1SMM, 1NMQ, 1NLQ, 1NPQ, 1SMQ, and 1SPQ - Aggregate Emissions Reports for Devices with District Assigned Device IDs

The Codes 1NMM and 1SMM data records are used to report monthly total NOx and SOx emissions, respectively, from all NOx and SOx Major Sources within a facility. The Codes 1NMQ, 1SMQ, 1NLQ, 1NPQ, and 1SPQ data records are used to report quarterly total NOx and SOx emissions, respectively, from all NOx and SOx Major, NOx Large Sources, and NOx and SOx Process Units within a facility. Starting January 1, 1998, these records shall be used to report aggregate emissions from applicable classification of devices within each facility.

Location Field Length Description
1-4 Record Identifier

4

1NMM, 1SMM, 1NMQ, 1SMQ, 1NLQ, 1NPQ, or 1SPQ
5-12 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
13-21 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
22 - 128 Filler

107

Blanks , used to fill unused remaining record positions

Code 1NXQ, 1SXQ, 1NTQ, 1STQ, 1NUQ, and 1SUQ - Aggregate Quarterly Emissions Reports for Devices without District Assigned Device IDs

The Code 1NXQ, 1SXQ, 1NTQ, 1STQ, 1NUQ, and 1SUQ data records are used to report quarterly total NOx and SOx emissions, respectively, from all Rule 219 exempt equipment, equipment operating under a various locations permit (e.g. rental equipment) and equipment without permit. Starting January 1, 1998, these records shall be used to report aggregate emissions from all applicable devices within each facility.

Location Field Length Description
1-4 Record Identifier

4

1NXQ, 1SXQ, 1NTQ, 1STQ, 1NUQ, and 1SUQ
5-12 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
13-21 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
22 - 128 Filler

107

Blanks , used to fill unused remaining record positions

Code 1NVF and 1SVF - NOx and SOx Emissions Reports by Fuel Type for Equipment Operated under a Various Locations Permit

The Code 1NVF and 1SVF data records are used to report NOx and SOx emissions, respectively, by fuel type from each device operating under a various location permit (e.g. rental equipment). Starting January 1, 1998, these records shall be used to report emissions from each device in this category.

Location Field Length Description
1-4 Record Identifier

4

1NVF or 1SVF
5-10 Permit Number

6

SCAQMD Permit Number. Left justified, blank filled
11-18 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
19-38 Fuel Type

20

Code for Fuel Type utilized. Left justified, blank filled
39-47 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
47 - 128 Filler

82

Blanks , used to fill unused remaining record positions

Code 1NVS and 1SVS - NOx and SOx Emissions Reports by SCC for Equipment Operated under a Various Locations Permit

The Code 1NVF and 1SVF data records are used to report NOx and SOx emissions, respectively, by SCC from each device operating under a various location permit (e.g. rental equipment). Starting January 1, 1998, these records shall be used to report emissions from each device in this category.

Location Field Length Description
1-4 Record Identifier

4

1NVS or SVS
5-10 Permit Number

6

SCAQMD Permit Number. Left justified, blank filled
11-18 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
19-26 SCC

8

Source Classification Code.
27-35 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
36 - 128 Filler

93

Blanks , used to fill unused remaining record positions

Code 1NRF, 1SRF, 1NWF, and 1SWF - NOx and SOx Emissions Reports by Fuel Type for Rule 219 Exempt Equipment, and Equipment Operated without a Permit

Code 1NRF, 1SRF, 1NWF, and 1SWF are used to report NOx and SOx emissions by fuel type from all devices which are exempt from permit under Rule 219 or from all devices operating without a permit. Starting January 1, 1998, these records shall be used to report emissions from all devices in each of these category.

Location Field Length Description
1-4 Record Identifier

4

1NRF, 1SRF, 1NWF, or 1SWF
5-12 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
13-32 Fuel Type

20

Code for Fuel Type utilized. Left justified, blank filled
33-41 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
42 - 128 Filler

82

Blanks , used to fill unused remaining record positions

Code 1NRS, 1SRS, 1NWS, and 1SWS - NOx and SOx Emissions Reports by SCC for Rule 219 Exempt Equipment, and Equipment Operated without a Permit

Code 1NRS, 1SRS, 1NWS, and 1SWS are used to report NOx and SOx emissions by SCC from all devices which are exempt from permit under Rule 219 or from all devices operating without a permit. Starting January 1, 1998, these records shall be used to report emissions from all devices in each of these category.

Location Field Length Description
1-4 Record Identifier

4

1NRS, 1SRS, 1NWS, or 1SWS
5-12 Date Emitted

8

End date of the reporting period in the format "YYYYMMDD"
13-20 SCC

8

Source Classification Code.
21-29 Total Emission

9(#######.##)

Enter the total emission in lb to 2 decimal places. Omit the decimal point, right justify and zero fill. No negative numbers.
30-128 Filler

99

Blanks , used to fill unused remaining record positions

Status Word Table

The Status Word Table is used to compile the status word for the required reporting period. True is 1 and False is 0.

Location Field Length Description
1-1 Valid Data

1

Enter true if valid data was obtained for the entire reporting period, else enter false
2-2 Calibration

1

Enter true if the monitoring system was calibrated during the reporting period, else enter false
3-3 Off-line

1

Enter true if the monitoring system was off-line at any time during the reporting period, else enter false.
4-4 Alternate Data Acquisition

1

Enter true if alternate data acquisition was used during the reporting period, else enter false.
5-5 Out of Control

1

Enter true if the CEMS was out of control during the reporting period, else enter false.
6-6 Fuel Switch

1

Enter true if more than one fuel type was used during the reporting period, else enter false.
7-7 10% range

1

Enter true if concentration was reported at 10% valid range when concentration value was below 10%, else enter false.
8-8 lower than 10% range

1

Enter true if concentration was reported at an actual value less than 10% valid range, else enter false.
9-9 non-operational

1

Enter true if the RECLAIM NOx source being monitored is non-operational for the entire day, else enter false.

Format for Correcting Emissions Reports

Name

Description

Record Identifier Record Identifier starting with "2"
Record to be corrected All information contained in previously submitted record which is to be corrected, except the original Record Identifier field and the filler field.
Correct Record The correct record containing all information for the record type, except the original Record Identifier field and the filler field.
Filler This field is blank filled to complete the 128 character fixed length reporting record.

Format for deleting Emissions Reports

Name

Description

Record Identifier Record Identifier starting with "3"
Record to be deleted All information contained in previously submitted record which is to be deleted, except the original Record Identifier field and the filler field.

APPENDIX G

DIAGRAMS

RTU
RTU